LFF
4-20 mA loss
Schindler · Altivar 312 Drive
¿Qué significa LFF ?
This fault indicates a loss of the 4-20 mA analog input signal, which is typically used for speed reference or process feedback. This can occur even if the [4-20mA loss] (LFL) parameter is set to [No] (nO) on page 95.
Causas comunes
- Disconnection or break in the 4-20 mA analog input wiring.
- Malfunction of the device providing the 4-20 mA signal.
- Incorrect wiring or configuration of the 4-20 mA input.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure the 4-20 mA signal directly at the drive's analog input terminals.
- 2
Check the wiring for the 4-20 mA analog input for continuity and correct connections.
- 3
Verify the settings of the analog input parameters.
Datos técnicos verificados. Última actualización: March 2026