Traduciendo...
SLF
MODBUS FAULT
Schindler · Altivar 312 Drive
¿Qué significa SLF ?
This fault indicates an interruption in communication on the Modbus bus. It can also be triggered if a remote display terminal is enabled ([HMI command] (LCC) = [Yes] (YES), page 61) but is disconnected.
Causas comunes
- Interruption or break in the Modbus communication bus cabling.
- Remote display terminal is disconnected while the [HMI command] (LCC) parameter (page 61) is set to [Yes] (YES).
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the physical connections and integrity of the Modbus communication bus.
- 2
Verify the link with the remote display terminal.
- 3
If a remote display is not used, ensure [HMI command] (LCC) is not set to [Yes] (YES).
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Schindler Altivar 312 Drive