F022

Modbus interruption

Schindler · Easy Altivar ATV310 Drive

¿Qué significa F022 ?

For the ATV310 drive, this fault occurs when communication on the Modbus network connected to the drive is interrupted. This can be due to physical connection issues, incorrect communication settings, or an improperly configured Modbus time-out.

Causas comunes

  • Interrupted communication on the Modbus network connected to the drive
  • Incorrect Modbus time out setting (parameter 704), leading to premature detection of communication loss

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check the physical connections (cabling, termination resistors) of the Modbus communication bus for integrity and proper wiring.

  2. 2

    Verify the Modbus time-out setting (parameter 704) in the ATV310 drive configuration to ensure it is appropriate for the network speed and master device.

  3. 3

    Consult the Modbus user manual for the ATV310 drive for detailed Modbus troubleshooting steps and wiring guidelines.