Overspeed
Schindler · Easy Altivar ATV310 Drive
¿Qué significa F025 ?
For the ATV310 drive, this fault indicates that the motor or application is operating at a speed significantly higher than expected, exceeding the drive's configured limits, potentially more than 10% above the Top frequency (parameter 308). This can be caused by control instability, high inertia loads, or incorrect speed loop parameters.
Causas comunes
- Instability in the speed control loop or application mechanics
- Overspeed associated with the inertia of the application, especially during deceleration
- Motor operating more than 10% above the configured Top frequency (parameter 308)
- Incorrectly tuned parameters of the speed loop (e.g., gain and stability settings)
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the motor operation and physical condition for any issues contributing to overspeed.
- 2
Adjust the Top frequency (parameter 308) if the motor is consistently operating more than 10% above its current setting, ensuring it matches application requirements.
- 3
Add a braking resistor to the drive, if not already present, to dissipate regenerative energy during deceleration and prevent overvoltage.
- 4
Check the sizing of the motor, drive, and load to ensure they are appropriate for the application's speed and inertia demands.
- 5
Review and re-tune the parameters of the speed loop (gain and stability) to ensure stable operation and prevent oscillations.