Traduciendo...
F31

AI L1 Over Voltage

Schneider Electric · XW Pro NA Operation Guide

¿Qué significa F31 ?

This fault indicates an L1 over-voltage condition (130 V) detected by the anti-islanding protection, triggering a slow disconnect. This mechanism ensures the inverter disconnects from an unstable grid, protecting both the inverter and grid from potential damage due to excessive voltage.

Causas comunes

  • Grid L1-Neutral voltage exceeding 130 V for a sustained period, indicating persistent grid voltage instability or a utility over-voltage condition.
  • Gradual voltage creep on phase L1 due to an imbalanced grid or nearby generator operations, exceeding the slow trip threshold.
  • Inverter's L1 voltage sensing circuit drifting out of calibration or experiencing intermittent measurement errors over time.
  • Anti-islanding parameter P_AI_L1_Volt_Max_Slow set too close to nominal, causing frequent trips during minor voltage fluctuations.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Using a true RMS multimeter, continuously monitor the L1-Neutral voltage at the inverter's AC input terminal L1 over several hours to detect persistent high voltage.

  2. 2

    Compare the sustained L1-Neutral voltage readings against the specified 130 V trip threshold and the inverter's P_AI_L1_Volt_Slow parameter.

  3. 3

    Verify that the neutral conductor connection to the inverter (Terminal N) and the L1 phase terminal (Terminal L1) are secure and free from corrosion.

  4. 4

    Contact the utility provider to report sustained high voltage conditions on phase L1 at your site and request a grid voltage stability check.

  5. 5

    If external voltage is stable, verify the inverter's internal L1 voltage measurement offset parameter (e.g., P_AI_L1_Volt_Offset) for potential misconfiguration.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Schneider Electric XW Pro NA Operation Guide