F93

SunSpec Controller Comms Lost

Schneider Electric · XW Pro NA Operation Guide

¿Qué significa F93 ?

This Automatic Fault occurs when communication with the SunSpec controller has been lost. This impacts data exchange and control for any SunSpec compliant devices integrated into the system.

Causas comunes

  • Communication cable (e.g., Modbus RTU RS485, Ethernet) between the SunSpec controller and the gateway/inverter is disconnected, damaged, or improperly terminated.
  • SunSpec compliant device (e.g., PV inverter, energy meter) has powered down, malfunctioned, or stopped responding to SunSpec queries.
  • Incorrect Modbus ID or IP address configured for the SunSpec device on the gateway or XW Pro (e.g., Parameter S1-01 for Modbus ID).
  • Gateway device failure to properly poll or relay data from the SunSpec controller due to internal fault.
  • Network or RS485 bus conflicts (e.g., duplicate Modbus IDs, excessive bus length, improper biasing or termination resistors).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Verify that the SunSpec controller and any associated devices are powered on and their communication indicators are active.

  2. 2

    2. Inspect the communication cable (e.g., RS485 A/B wires, Ethernet) between the SunSpec controller and the inverter/gateway for physical damage and secure connections.

  3. 3

    3. Check the Modbus ID (e.g., Parameter S1-01) or IP address configured in the inverter/gateway for the SunSpec device and ensure it matches the actual device setting.

  4. 4

    4. Using a Modbus testing tool, attempt to communicate directly with the SunSpec controller to verify its responsiveness.

  5. 5

    5. Power cycle the SunSpec controller and the gateway/inverter to reset communication modules and re-establish connection.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Schneider Electric XW Pro NA Operation Guide