A07927

DC braking active

Siemens · DCM

¿Qué significa A07927 ?

The motor is currently being braked using DC current, which is a normal operational state. This alarm appears when a message with a 'DCBRK' response is active, injecting the braking current (p1232) for a duration (p1233) or until the standstill threshold (p1226) is undershot. It can also be activated manually via binector input p1230. This is an informational alarm and does not indicate a fault.

Causas comunes

  • DC braking command activated (e.g., via digital input, PLC command, or internal function) as part of a normal machine stop sequence.
  • Parameter P1230 (DC braking switch on) or P1231 (DC braking switch on for braking ramp) enabled, causing DC braking to engage automatically.
  • Braking current (P1232) or braking time (P1233) configured and actively being injected into the motor windings.
  • A safety function (e.g., STO - Safe Torque Off) or protection function triggering a controlled stop which includes DC braking.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Verify the active command source for DC braking (e.g., check status of digital input BICO-connected to P1230).

  2. 2

    2. Review parameter P1230 (DC braking switch on) to confirm whether DC braking is enabled by an external signal or automatically.

  3. 3

    3. Check parameter P1231 (DC braking switch on for braking ramp) to see if DC braking is configured for automatic activation after deceleration.

  4. 4

    4. Observe the motor current (r0027) during the 'DC braking active' alarm to confirm DC current injection.

  5. 5

    5. If this alarm is unexpected, investigate the machine's control logic (PLC program) to identify the condition triggering the DC braking command.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026