Traduciendo...
2

Overvoltage

Vacon · NX Liquid-Cooled Drive

¿Qué significa 2 ?

The DC-link voltage has exceeded its predefined limits. This often occurs due to overly short deceleration times during motor stopping, or significant overvoltage spikes originating from the mains supply. For 400-500Vac mains, a fault trips at 911Vdc (warning at 860Vdc); for 500-690Vac mains, a fault trips at 1250Vdc (warning at 1150Vdc). Subcodes S1 (hardware trip) and S2 (overvoltage control supervision) provide additional diagnostic context.

Causas comunes

  • DC bus voltage exceeding maximum limits during regeneration.
  • Incorrect braking resistor selection or connection.
  • Power grid voltage significantly higher than nominal.
  • Parameter P1-03 (Max voltage) set too low.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Increase the deceleration time parameter in the drive configuration to allow for slower motor braking.

  2. 2

    Install a brake chopper and/or brake resistor if not already present, or verify their operation if installed. For INU devices, ensure overvoltage control is set to active.

  3. 3

    Measure the incoming AC supply voltage at the drive input terminals to check for transient spikes or sustained high voltage.

Ver todos los códigos en este manual (52)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas