Earth Fault

Vacon · NX Liquid-Cooled Drive

¿Qué significa 3 ?

The current measurement system has detected that the sum of the motor phase currents is not zero, indicating a leakage current to ground. This fault is most commonly caused by insulation failure in the motor cables or within the motor windings themselves.

Causas comunes

  • Insulation failure in motor windings or power cables.
  • Ground fault in the connected equipment.
  • Moisture or contamination ingress into electrical components.
  • Faulty grounding connection.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the insulation resistance between each motor phase cable (U, V, W) and ground (PE) using a megger.

  2. 2

    Measure the insulation resistance between each motor winding (U, V, W) and the motor frame (PE) with a megger.