43
Encoder fault
Vacon · NX Liquid-Cooled Drive
¿Qué significa 43 ?
A problem has been detected in the encoder signals. Subcodes in T.14 specify the issue: S1 (Encoder 1 channel A missing), S2 (Encoder 1 channel B missing), S3 (Both encoder channels missing), S4 (Encoder reversed), S5 (Encoder board missing), S6 (Serial communication fault), S7 (Channel A/B mismatch), S8 (Resolver/Motor pole pair mismatch), or S9 (Missed start angle).
Causas comunes
- Encoder signal loss or corruption.
- Encoder connection faulty or disconnected.
- Encoder power supply out of range.
- Encoder internal fault detected.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check all encoder channel connections at both the drive's input terminals and the encoder itself for integrity and proper signal transmission.
- 2
Inspect the encoder board for correct seating within its slot and any signs of physical damage.