Traduciendo...
oL3

Overtorque Detection 1

Yaskawa · V1000

¿Qué significa oL3 ?

This fault indicates that the drive's output current exceeded the level set in L6-02 for longer than the time specified in L6-03. This suggests a mechanical issue like a machine lock-up or that the load parameters are incorrectly configured. Leaving this unresolved can lead to continued machine stress, overheating, or damage to connected equipment.

Causas comunes

  • Mechanical jam or excessive friction in the driven equipment (e.g., conveyor, pump, fan impeller).
  • Motor or drive is undersized for the peak torque requirements of the application.
  • Rapid acceleration rate (e.g., C1-01) set too fast for the load's inertia.
  • Incorrect overtorque detection level (L6-02) set too low, or overtorque detection time (L6-03) set too short.
  • Worn bearings in the motor or gearbox increasing frictional load.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Manually attempt to rotate the load mechanism to identify any mechanical binding or obstruction.

  2. 2

    2. Monitor the drive's output current (e.g., display parameter U1-06) during operation and compare to motor nameplate rated current.

  3. 3

    3. Increase parameter L6-02 (Overtorque Detection 1 Level) or L6-03 (Overtorque Detection 1 Time) in small increments if mechanical inspection yields no fault.

  4. 4

    4. Verify acceleration time parameter C1-01 is appropriate for the load inertia; increase it if acceleration is too rapid.

  5. 5

    5. Perform a load test without the motor connected to the mechanical system if possible, to isolate the motor/drive from the load.

  6. 6

    6. Check motor parameters P1-01 through P1-08 for accuracy against the motor nameplate.

Ver todos los códigos en este manual (87)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas