Low-voltage of Control Power Supply (ECM)
Fanuc · A20B-2101-0390 αi series AC Servo Motor and Spindle
What does 5 mean?
The 24V control power supply voltage to the ECM has dropped below the acceptable threshold. This can lead to improper operation or shutdown of the ECM.
Repair Steps
- 1
Measure the 24V control power supply voltage at the input terminals to the ECM.
- 2
Check the external 24V power supply unit for proper operation and load capacity.
- 3
Inspect the wiring from the 24V power supply to the ECM for voltage drops or loose connections.