SP0757

SAFETY SPEED OVER

Fanuc · αi Series Servo Amplifier

What does SP0757 mean?

The CNC CPU detected that the spindle motor speed on the n-th spindle was greater than the safety speed (parameter No. 4372, 4438, 4440, or 4442) during safety monitoring (when the safety check request signal (*VLDPs) is 0). This indicates an unsafe spindle operating speed, which is a critical safety violation.

Repair Steps

  1. 1

    Verify the values set for safety speed parameters No. 4372, 4438, 4440, or 4442.

  2. 2

    Ensure that spindle operation is programmed and executed within the defined safety speed limits.

Browse all codes in this manual (101)
Verified technical data. Last updated: March 2026
Source: Fanuc αi Series Servo Amplifier