607 n AXIS: CNV. SINGLE PHASE FAILURE

CONVERTER SINGLE PHASE FAILURE

Fanuc · Series 0i-D/0i Mate-D Maintenance

What does 607 n AXIS: CNV. SINGLE PHASE FAILURE mean?

This warning signal on the Fanuc Series 0i-D/0i Mate-D αi servo system indicates a loss of one phase in the input power supply to the converter (SVWRN4, SVWRN3, SVWRN2, SVWRN1 active). Depending on the Power Supply Module (PSMR/PSM), an alarm will occur within five seconds to one minute.

Common Causes

  • Loss of one phase in the incoming three-phase AC power supply.
  • Faulty or tripped upstream circuit breaker or fuse for one phase.
  • Poor contact or failure in a magnetic contactor supplying power to the converter.
  • Loose or damaged power wiring connections to the converter.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Measure the incoming three-phase AC supply voltage at the converter's input terminals to verify all phases are present and balanced.

  2. 2

    Inspect all input power connections to the converter for looseness, corrosion, or damage, including fuses and circuit breakers.

  3. 3

    Check the operation of any upstream contactors or protective devices for proper functionality and contact integrity.

  4. 4

    Verify that the main power supply to the machine is stable and not experiencing sags or interruptions on one phase.

  5. 5

    If input power is confirmed stable and correctly connected, inspect the converter unit for internal damage if the issue persists.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026

Related Faults

Source: Fanuc Series 0i-D/0i Mate-D Maintenance