No LED Display

No LED Display on Power Supply

Fanuc · Series 30i/31i/32i-MODEL B Plus

What does No LED Display mean?

This condition occurs when the 200-V control power (CX1A) is not supplied to the α i PS or α i PSR unit, or when the 24-VDC power output is short-circuited. This prevents the Power Supply from operating and indicating status.

Common Causes

  • The circuit breaker for the 200-V control power supply is off.
  • A lightning surge absorber connected immediately after the circuit breaker is short-circuited.
  • The 24-V power to a Servo Amplifier or Spindle Amplifier is short-circuited.
  • External 24-V power is incorrectly connected to pin 3 of connector CX4.

Repair Steps

  1. 1

    Check whether the circuit breaker for the control power supply is off.

  2. 2

    If a lightning surge absorber is connected immediately following the circuit breaker, check whether the lightning surge absorber is short-circuited. Replace it if short-circuited.

  3. 3

    Disconnect the cable from connector CX1A and turn the control power on. If '-' is displayed, detect the amplifier which causes the 24-V power to be short-circuited by sequentially connecting the cable from the Power Supply and replace it.

  4. 4

    Disconnect the cable from connector CX4 and turn the control power on. If '-' is displayed, correct the connection of the external 24-V power to pin 3 of CX4.

Browse all codes in this manual (38)
Verified technical data. Last updated: March 2026
Source: Fanuc Series 30i/31i/32i-MODEL B Plus