What does 2082 mean?
The inverter fails to communicate with the Smart Backup Box or an unrecoverable fault occurs on a circuit inside the Smart Backup Box. This impacts the inverter's ability to operate in grid-tied or off-grid modes.
Common Causes
- The inverter fails to communicate with the Smart Backup Box.
- An unrecoverable fault occurs on a circuit inside the Smart Backup Box.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Send a shutdown command on the app. Turn off the AC output switch, DC input switch, and battery switch.
- 2
Check whether the power cable and RS485 cable between the Smart Backup Box and the inverter are normal.
- 3
After 5 minutes, turn on the battery switch, AC output side, AC output switch, and DC input switch.