59

59 Parallel Coil Fault

Kone · Elevator Control

What does 59 mean?

A fault has been detected in the parallel coil, indicating an electrical issue with this specific solenoid. This disables both lifting and driving functions.

Common Causes

  • Parallel coil open circuit, short circuit, or high resistance.
  • Damaged wiring or loose connections to the parallel coil.
  • Control circuit failure attempting to activate the coil.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the identification and physical location of the 'parallel coil' solenoid within the Kone Kone Elevator Control system schematics.

  2. 2

    Inspect all associated wiring, connectors, and terminals of the parallel coil solenoid for damage, loose connections, or corrosion.

  3. 3

    De-energize the system. Measure the resistance of the parallel coil solenoid across its terminals and compare the reading to the nominal value specified in the electrical documentation.

  4. 4

    Energize the system. Measure the supply voltage at the parallel coil solenoid terminals when commanded to activate, ensuring it matches the specified operating voltage.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026