What does 11007 mean?

The PROFINET device configured in the controller's software does not match the actual physical device connected at the specified Slot and Subslot for {Name}. This configuration discrepancy prevents correct communication and operation of the device.

Repair Steps

  1. 1

    Compare the configured device type and model in WorkVisual for device {Name} at Slot {Slot}, Subslot {Subslot} with the actual device nameplate information.

  2. 2

    Update the PROFINET configuration in WorkVisual to precisely match the physically connected device's identity at the specified slot and subslot.

  3. 3

    Ensure the GSDML file used for device {Name} in the PROFINET project is the correct version for the installed hardware.