087

Sd7

Lenze · 9300 Series

What does 087 mean?

An initialization error occurred at the absolute value encoder at X8, or the encoder electronics are defective. This can result from a loose cable, an open circuit, an incorrect encoder type, or failure during rotor position adjustment.

Common Causes

  • Encoder cable disconnection: Loose connection at encoder connector (e.g., X8) or at the encoder side, causing complete signal loss.
  • Open circuit in cable: One or more conductors (e.g., power, ground, data lines) in the absolute encoder cable are broken, preventing communication.
  • Incorrect encoder type: An unsupported or incompatible absolute encoder type is connected to terminal X8, or the encoder selection parameter (e.g., P4-10) is set incorrectly.
  • Encoder power supply issue: The encoder's internal electronics are not receiving sufficient voltage (e.g., 5V or 24V supply via X8/1 and X8/2) due to a short or fault.
  • Defective encoder hardware: The absolute encoder itself has an internal electronic failure and is not transmitting valid initialization data.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify all connections at terminal X8 on the device and at the absolute encoder connector, ensuring they are tight and properly seated (e.g., visual inspection for loose pins).

  2. 2

    Using a multimeter, measure the resistance and continuity of each conductor in the encoder cable from X8 to the encoder, paying attention to power (e.g., +5V/24V) and data lines.

  3. 3

    Measure the supply voltage delivered to the encoder via X8 (e.g., +5V or +24V between pins X8/1 and X8/2) to ensure it is stable and within specification.

  4. 4

    Check the encoder type selection parameter (e.g., P4-10 or encoder initialization parameters) to ensure it matches the connected absolute encoder model.

  5. 5

    If possible, swap the suspected absolute encoder with a known-good encoder of the same type to isolate whether the fault is with the encoder or the drive's input.

Browse all codes in this manual (145)
Verified technical data. Last updated: March 2026

Related Faults

Lenze Error 087: Sd7 — Troubleshooting Guide | ErrorLib