CE2

CAN2_IN communication error

Lenze · 9300 Series

What does CE2 mean?

The CAN2_IN object is receiving faulty data or communication is interrupted. This is likely caused by wiring issues at X4, a faulty sender, or an insufficient monitoring time for the communication, leading to unreliable data exchange.

Common Causes

  • CAN2_IN communication bus failure between devices.
  • Faulty CAN transceiver on connected devices.
  • Wiring issue on the CAN2_IN bus (shorts, opens).
  • Termination resistor issues on the CAN2_IN bus.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check wiring at X4 for proper connections and integrity.

  2. 2

    Check the sender device for correct operation and data transmission.

  3. 3

    Increase monitoring time under C0357/2, if necessary, to account for communication delays.

  4. 4

    Switch off monitoring by setting C0592 = 3.

Browse all codes in this manual (145)
Verified technical data. Last updated: March 2026

Related Faults