I²xt overload
Lenze · 9300 Series
What does OC6 mean?
This fault signifies a cumulative thermal overload condition based on the square of current and time, resulting from frequent and prolonged acceleration processes with motor overcurrent or permanent motor overload with Imotor > Irmotor. This can severely stress the motor and drive components.
Common Causes
- Continuous motor operation above its rated current (e.g., Imotor > 1.05 x C0203) for extended periods, leading to thermal buildup.
- Frequent and heavy acceleration/deceleration cycles that repeatedly push the motor current significantly above its nominal value.
- Motor cooling fan failure or obstructed ventilation preventing adequate heat dissipation from the motor windings.
- High ambient temperature (e.g., >40°C) surrounding the motor and drive, reducing their effective thermal capacity.
- Incorrect motor thermal model parameters in the drive (e.g., C0203, P1-54, P1-55) not accurately reflecting the motor's characteristics.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Monitor the motor current (C0004) and motor temperature (C0005, if sensor connected) during operation to identify sustained overload conditions.
- 2
Reduce the mechanical load on the motor if possible, or consider upsizing the motor to match the application requirements.
- 3
Increase acceleration and deceleration ramp times (e.g., C0256, C0257) to lower peak currents during dynamic operations.
- 4
Inspect the motor's cooling fan for proper operation and ensure that air vents on both the motor and drive are clear of obstructions.
- 5
Verify that the motor rated current (C0203) is correctly entered into the drive and that any service factor settings (P1-54, P1-55) are appropriate for the motor.