0x2350
CiA: i²xt overload (thermal state)
Lenze · i550 protec Drive
What does 0x2350 mean?
This fault signifies a thermal overload of the motor, typically caused by an impermissible continuous current or by frequent or excessively long acceleration processes. The drive is disabled, and the motor will coast. This fault is configurable and requires a blocking time of 5 seconds before reset.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Verify and correct the motor data settings in the inverter configuration.
- 4
Reduce values for slip compensation parameters 0x2B09:001 (P315.01) and 0x2B09:002 (P315.02).
- 5
Reduce values for oscillation damping parameters 0x2B0A:001 (P318.01) and 0x2B0A:002 (P318.02).
Source: Lenze i550 protec Drive
Open Manual (Page 614)