Motor blocked
Lenze · SHB4800/4900
What does dEr mean?
This fault indicates that the motor's shaft is prevented from rotating or is rotating significantly slower than commanded, likely due to a mechanical obstruction or excessive load. By default, this critical condition triggers a full TRIP, inhibiting all ignition pulses and resetting the Ready signal to prevent motor damage, overheating, or mechanical stress on the system. Manual reset is required.
Complete Troubleshooting Guide
- 1
Check for mechanical obstructions: Visually inspect the motor, coupling, and driven machinery for any jams, foreign objects, or binding.
- 2
Disengage load (if possible): Attempt to disconnect the motor from the load to determine if the motor can rotate freely on its own.
- 3
Verify motor brake operation: If a motor brake is present, ensure it is releasing fully when commanded.
- 4
Measure motor current: Monitor motor current during attempted start to detect high currents indicating mechanical resistance.
- 5
Check motor bearings: Listen for unusual noises from the motor bearings that could indicate failure.