OH4
Heatsink overtemperature (C0122)
Lenze · SM29_05 Service Bulletin
What does OH4 mean?
The heatsink temperature has exceeded the threshold set in C0122. Causes include ambient temperatures above +40°C or +50°C, a dirty heatsink, an incorrect mounting position, or the value specified under C0122 being set too low.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Clean the heatsink if it is very dirty to improve heat dissipation.
- 4
Change the mounting position if it is hindering airflow.
- 5
Enter a higher value under C0122 if the threshold is set too low.
- 6
Switch off monitoring by setting C0582 = 3.
Source: Lenze SM29_05 Service Bulletin