E.SAF
Safety circuit fault
Mitsubishi Electric · FR E700
What does E.SAF mean?
This safety circuit fault appears when the internal safety circuit malfunctions, or when protective lines (S1-PC, S2-PC) are open. It can also be triggered by a prolonged 24V external power supply start-up time. This is a critical safety integrity issue, preventing normal operation.
Complete Troubleshooting Guide
- 1
If the safety stop function is not utilized, ensure that shorting wires are correctly installed between terminals S1 and PC, and S2 and PC.
- 2
If the safety stop function is active, verify the wiring of terminals S1, S2, and PC, and confirm proper operation of the safety relay module or other safety input signal sources.
- 3
For 24V external power supply operation, ensure its start-up time is configured to be within 500ms.