113XH

Input Response Time Range Error

Mitsubishi Electric · MELSEC iQ-R I/O Module

What does 113XH mean?

A value outside the permissible range of 0 to 4 has been configured for the 'Input response time X' parameter, where 'X' denotes a specific input terminal. This error can also occur if the 'Input response time X' is set shorter than the calculated input dark test pulse output time, which is derived from 'Input dark test pulse OFF time' and 'Number of pulse output for input dark test'.

Common Causes

  • The 'Input response time X' parameter for a specific input terminal X is set to a value less than 0.
  • The 'Input response time X' parameter for a specific input terminal X is set to a value greater than 4.
  • The 'Input response time X' parameter is set to a shorter duration than the 'Input dark test pulse output time' (Input dark test pulse OFF time × ((Number of pulse output for input dark test × 2) - 1)).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Set the 'Input response time X' parameter within the valid range from 0 to 4 for the affected input terminal.

  2. 2

    Ensure the 'Input response time X' is set to a longer time than the calculated 'Input dark test pulse output time'.

Browse all codes in this manual (56)
Verified technical data. Last updated: March 2026

Related Faults

Source: Mitsubishi Electric MELSEC iQ-R I/O Module