Output dark test error
Mitsubishi Electric · MELSEC iQ-R I/O Module
What does 2003H mean?
During an output dark test, the expected test pulses were not detected. This signifies that the output circuit did not respond correctly to a diagnostic test, potentially due to wiring faults, issues with connected devices, or an internal hardware problem.
Common Causes
- An unused output terminal is not configured with 'Not used' in 'Wiring output selection'.
- Faulty connected devices or incorrect wiring on the output terminal.
- Influence from electrical noise affecting the output dark test pulses.
- An internal hardware error within the I/O module with diagnostic functions.
Repair Steps & Checklist
Click steps to track your progress.
- 1
For any unused output terminals, ensure 'Not used' is selected for 'Wiring output selection'.
- 2
Identify the specific terminal experiencing the error using 'Output dark test error detection state' (Un\G1540), then inspect and adjust connected devices and wiring.
- 3
Implement measures to mitigate electrical noise, such as shielding cables or isolating power supplies.
- 4
If the error persists after noise mitigation, the module may require replacement due to a hardware failure.