F10E
Number of Receive Error Retries Exceeded
Mitsubishi Electric · MELSEC Q-series MELSECNET/H
What does F10E mean?
The system has attempted to receive data multiple times but consistently failed, exceeding the allowed number of retries. This suggests a persistent communication issue on the receiving end.
Common Causes
- Persistent network communication problems preventing successful data reception
- Faulty cables or incorrect wiring
- Absence of terminating resistors (in bus networks)
- Duplicate station numbers or duplicate control/master stations
- Faulty network hardware at the receiving station
Repair Steps & Checklist
Click steps to track your progress.
- 1
Inspect network cables for physical faults or incorrect wiring
- 2
Verify the presence and correct installation of terminating resistors on the bus network
- 3
Check for sources of electrical noise near network cabling
- 4
Verify station numbers and control/remote master station settings for any duplication
- 5
Check for faulty network hardware at the receiving station
Verified technical data. Last updated: March 2026