7002

Multiple CPU System Initial Communication Error

Mitsubishi Electric · MELSEC System Q/L Series

What does 7002 mean?

This fault signifies a failure in the initial communication process between CPU modules in a multiple CPU system. It is triggered by a lack of response from a target CPU module or the presence of an incompatible CPU module within the system. The error occurs at power ON or reset, causing the multiple CPU system to stop.

Common Causes

  • No response received from the target CPU module during initial communication within the multiple CPU system.
  • A CPU module incompatible with the multiple CPU system was mounted.
  • Potential hardware fault in any of the CPU modules if the error persists after other corrective actions.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Reset the CPU module and attempt to transition it to RUN mode again.

  2. 2

    Remove any CPU module identified as incompatible with the multiple CPU system from the main base unit.

  3. 3

    Replace any CPU module incompatible with the multiple CPU system with a compatible one.

  4. 4

    Verify all communication cabling between CPU modules for proper connection and integrity.

Browse all codes in this manual (53)
Verified technical data. Last updated: March 2026