Current Sensor Error / Outdoor Fan Motor Anomaly
Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit
What does U8 (00) mean?
This code indicates either an abnormal current detection by the current sensor (-1.5A to 1.5A) during compressor operation, or an abnormal rotational frequency of the outdoor fan motor. Fan motor abnormality occurs if rotation is below 100 rpm for 1 second at >=20°C ambient temperature, or below 80 rpm / above 1300 rpm continuously for 1 minute. Potential root causes include incorrect compressor wiring, a defective current sensor circuit on the outdoor power circuit board, DC fan motor failure, or an issue with the outdoor circuit controller board.
Common Causes
- Current sensor fault or anomaly detected (U8 code).
- Outdoor fan motor operating outside expected parameters or has an internal fault.
- Interference or signal loss from the outdoor fan motor control.
- Possible issue with the outdoor fan motor's speed or direction feedback.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Correct the U·V·W phase wiring to the compressor. Refer to section 10-9 for the Outdoor power circuit board.
- 2
Check or replace the DC fan motor.
- 3
Check the voltage of the outdoor circuit controller board during operation.
- 4
Replace the outdoor power circuit board if the current sensor issue persists after verifying wiring.
- 5
Replace the outdoor circuit controller board if the fan motor failure persists after checking/replacing the motor.