Overheat protection (Outdoor pipe thermistor)
Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit
What does Ud mean?
This fault triggers if the outdoor pipe thermistor (TH1) detects 70°C (158°F) or more during compressor operation. It indicates excessive heat within the outdoor unit, likely due to restricted airflow, a malfunctioning outdoor fan, or a faulty thermistor. Persistent overheating can lead to compressor failure and significant reduction in cooling efficiency.
Complete Troubleshooting Guide
- 1
Inspect the outdoor unit's air passage for any obstructions, dirt, or debris.
- 2
Verify proper operation of the outdoor fan motor and fan blades.
- 3
Check the outdoor pipe thermistor (TH1) for correct resistance values and secure connections.
- 4
Turn the unit off and on again. If the error code reappears, address the root cause, possibly replacing the thermistor if it's faulty.