UF (100)

Compressor Overcurrent Interruption (Locked)

Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit

What does UF (100) mean?

An overcurrent condition on the DC bus or compressor is detected within 30 seconds after the compressor starts operating. This indicates a locked compressor state. Common causes include a closed stop valve, decreased power supply voltage, loose, disconnected, or reversed compressor wiring connection, a defective compressor, or a faulty outdoor power board.

Common Causes

  • Compressor is drawing excessive current, potentially locked or overloaded (UF code).
  • Mechanical binding or seized compressor rotor.
  • High differential pressure across the compressor.
  • Over-temperature condition within the compressor windings.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Open the stop valve.

  2. 2

    Check the facility of the power supply.

  3. 3

    Correct the U·V·W phase wiring to the compressor. Refer to section 10-9 (Outdoor power circuit board).

  4. 4

    Check the compressor. Refer to section 10-6.

  5. 5

    Replace the outdoor power circuit board.

Browse all codes in this manual (45)
Verified technical data. Last updated: March 2026

Related Faults

Source: Mitsubishi Electric PUZ-HA30/36NHA4 Outdoor Unit