E.OLT
Stall prevention stop
Mitsubishi Electric · FR E700
What does E.OLT mean?
This stall prevention stop fault occurs if the inverter's output frequency drops to 1Hz and remains there for 3 seconds due to active stall prevention. It indicates a prolonged and severe overload condition on the motor, which can lead to motor and inverter stress if unaddressed.
Repair Steps
- 1
Reduce the mechanical load on the motor to bring it within the inverter's capacity.
- 2
Review and adjust the Pr. 22 (Stall prevention operation level) setting to ensure it is appropriate for the application.
Verified technical data. Last updated: March 2026
Source: FR E700