E.OPT
Option alarm
Mitsubishi Electric · Mitsubishi A500 Inverter
What does E.OPT mean?
The inverter output is stopped if two or more communication options are fitted simultaneously (with specific exceptions like FR-A5NR). If a high power factor converter is connected, this alarm also triggers if an AC power supply is accidentally connected to the R, S, T (<L1, L2, L3>) terminals.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Check the setting of parameter Pr. 30 and verify all associated wiring for correctness.
Source: Mitsubishi A500 Inverter
Open Manual (Page 200)