UL

Abnormal low pressure (Low-pressure switch activated)

Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit

What does UL mean?

The 63L low-pressure switch activates, indicating system pressure below -0.07 MPa (-10 PSIG) during compressor operation. This critical fault suggests a closed outdoor unit stop valve, significant refrigerant leakage/shortage, or a malfunction in the linear expansion valve. Ignoring this can lead to severe and irreparable damage to the compressor.

Repair Steps

  1. 1

    Verify that the stop valve of the outdoor unit is fully open.

  2. 2

    Check the connector (63L) on the outdoor controller board and the 63L low-pressure switch itself for secure connections and proper function.

  3. 3

    Check the system for refrigerant leakage and correct the refrigerant amount to the proper level.

  4. 4

    Inspect and test the linear expansion valve for proper operation. Refer to Section 10-6.

  5. 5

    If all other components are confirmed functional, replace the outdoor controller board.