E38

Outside Air Temperature Sensor (ThOA) Defective

Mitsubishi Electric · R410A Systems

What does E38 mean?

The outdoor ambient air temperature sensor (ThOA) is defective (resistance is open circuit) or has a poor connection to the outdoor unit PCB. This impacts the system's ability to adjust operation based on ambient conditions, affecting efficiency.

Repair Steps

  1. 1

    Measure the resistance of the ThOA sensor at its leads — compare to a resistance-temperature chart if available.

  2. 2

    Inspect the ThOA sensor's connector on the outdoor unit PCB — verify it is securely seated and free from corrosion.

  3. 3

    Check for damage to the sensor wiring between the sensor and the PCB using a multimeter for continuity.