E39

Compressor Discharge Temperature Sensor (THOD) Defective

Mitsubishi Electric · R410A Systems

What does E39 mean?

The compressor discharge temperature sensor (THOD) is defective (resistance is open circuit) or has a poor connection to the outdoor unit PCB. This prevents accurate monitoring and protection of compressor discharge temperature, risking compressor damage.

Repair Steps

  1. 1

    Measure the resistance of the THOD sensor at its leads — compare to a resistance-temperature chart if available.

  2. 2

    Inspect the THOD sensor's connector on the outdoor unit PCB — verify it is securely seated and free from corrosion.

  3. 3

    Check for damage to the sensor wiring between the sensor and the PCB using a multimeter for continuity.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026
Source: Mitsubishi Electric R410A Systems