E45
Inverter to Outdoor PCB Transmission Error
Mitsubishi Electric · R410A Systems
What does E45 mean?
A communication error has occurred between the inverter and the outdoor unit PCB, possibly due to a loose connection at the Cn1 terminal. This disrupts the control of the compressor by the inverter.
Repair Steps
- 1
Inspect the Cn1 connector on both the outdoor unit PCB and the inverter board — verify it is securely seated.
- 2
Check the continuity and integrity of the wiring connected to Cn1 using a multimeter.
- 3
Verify stable power supply to both the inverter board and the outdoor unit PCB.
Verified technical data. Last updated: March 2026
Source: Mitsubishi Electric R410A Systems