E.IOH
Inrush Current Limit Circuit Overheat
Mitsubishi · FR-E800 Variable Frequency Drive
What does E.IOH mean?
The inverter output is shut off when the resistor in the inrush current limit circuit has overheated, indicating a fault within this circuit. This typically results from frequent power ON/OFF cycles or a damaged component within the inrush current path. Continued operation with this fault risks further component damage.
Complete Troubleshooting Guide
- 1
Review the application and modify the control logic to prevent frequent power ON/OFF cycles to the inverter.
- 2
Check for a blown 5A input fuse in the power supply circuit for the inrush current limit contactor.
- 3
Inspect the power supply circuit and contactor of the inrush current limit for any physical damage.
- 4
If the problem persists after these steps, contact your sales representative.