E.OPT

Option Fault

Mitsubishi · FR-E800 Variable Frequency Drive

What does E.OPT mean?

This fault appears under several conditions: if a plug-in option for torque command is selected (Pr.804) but no option is mounted, if a manufacturer setting switch on a plug-in option is changed, or if a communication option is connected while Pr.296 (Password lock level) is set to '0' or '100'. It indicates an incorrect configuration or an issue with an installed option.

Complete Troubleshooting Guide

  1. 1

    Verify that the plug-in option for torque command setting is correctly connected and check the Pr.804 setting.

  2. 2

    Reset any manufacturer setting switches on the plug-in option back to their initial settings.

  3. 3

    To apply a password lock when installing a communication option, set Pr.296 to a value other than '0' or '100'.