E.PUE
PU Disconnection / RS-485 Communication Fault
Mitsubishi · FR-E800 Variable Frequency Drive
What does E.PUE mean?
The inverter output is shut off because communication between the inverter and the Parameter Unit (PU) has been suspended, or RS-485 communication errors exceeded the retry count or check time. This occurs when Pr.75 has PU disconnection detection enabled, or if Pr.121 or Pr.122 settings for RS-485 communication are exceeded. It indicates a loss of control or monitoring via the PU/RS-485 link.
Complete Troubleshooting Guide
- 1
Review and adjust the setting of Pr.75 Reset selection/disconnected PU detection/PU stop selection as necessary.
- 2
Ensure the PU cable is securely connected.
- 3
For RS-485 communication, check the settings of Pr.121 PU communication retry count and Pr.122 PU communication check time interval.