E.USB
USB Communication Fault
Mitsubishi · FR-E800 Variable Frequency Drive
What does E.USB mean?
The inverter output has shut off because USB communication was interrupted for a duration exceeding the time set in Pr.548 USB communication check time interval. This indicates a break in the USB connection or an incorrectly configured communication watchdog timer. Loss of communication will prevent external control and monitoring.
Complete Troubleshooting Guide
- 1
Verify that the USB communication cable is securely connected at both ends.
- 2
Check the setting of Pr.548 USB communication check time interval.
- 3
If intermittent disconnections are expected or tolerated, increase the Pr.548 setting or set it to "9999" to disable the communication check.