Ed (00)

Serial communication error

Mitsubishi Electric · Mitsubishi PUZ-HA30-36NHA4 Outdoor Unit

What does Ed (00) mean?

This error indicates a failure in serial communication. It can occur between the outdoor controller circuit board and the outdoor power circuit board, or between the outdoor controller circuit board and the M-NET board. Causes include broken wires, contact failures in connectors (CN, CNMNT, CND), defective communication circuits on the boards, or noise interference on the M-NET transmission wire.

Additional Steps

Steps 1–2 are listed in Priority Fix.

  1. 3

    Review the M-NET transmission wiring method for proper installation.

  2. 4

    If communication between the outdoor controller and outdoor power board fails, replace the outdoor power circuit board.

  3. 5

    If communication between the outdoor controller and outdoor power board fails, replace the outdoor controller circuit board.