Abnormal Heatsink Temperature
Mitsubishi Electric · Mitsubishi PUZ-HA30-36NHA4 Outdoor Unit
What does U5 mean?
The heatsink thermistor (TH8) detects an abnormal temperature, either too low (below -40°F [-40°C]) or too high (above 183°F [84°C]). This indicates a potential issue with the outdoor fan, restricted airflow, excessive ambient temperature (above 114°F [46°C]), or a fault in the thermistor or associated circuit boards.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Verify the ambient temperature around the outdoor unit to ensure it is within the specified operating limits (e.g., upper limit 114°F [46°C]).
- 4
Measure the resistance value of thermistor TH8 and compare it to expected values for the measured temperature.
- 5
If the outdoor fan, airflow, and thermistor are confirmed normal, replace the outdoor power circuit board.
- 6
If fan drive is faulty, replace the outdoor controller circuit board.