UF (100)
Compressor Overcurrent Interruption (Locked)
Mitsubishi Electric · Mitsubishi PUZ-HA30-36NHA4 Outdoor Unit
What does UF (100) mean?
An overcurrent condition on the DC bus or compressor is detected within 30 seconds after the compressor starts operating. This indicates a locked compressor state. Common causes include a closed stop valve, decreased power supply voltage, loose, disconnected, or reversed compressor wiring connection, a defective compressor, or a faulty outdoor power board.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
Correct the U·V·W phase wiring to the compressor. Refer to section 10-9 (Outdoor power circuit board).
- 4
Check the compressor. Refer to section 10-6.
- 5
Replace the outdoor power circuit board.
Source: Mitsubishi PUZ-HA30-36NHA4 Outdoor Unit
Open Manual (Page 28)