0017

NVRAM/MEMORY MODULE USER PROGRAM MISMATCH

Allen-Bradley · MicroLogix 1400 Programmable Controllers

Hva betyr 0017 ?

Status bit S:2/9 is set in the controller, indicating that the user program stored in the non-volatile RAM (NVRAM) or memory module does not match the user program currently loaded and executing in the controller. This is a nonrecoverable fault.

Vanlige årsaker

  • User program on the memory module is different from the controller's active program.
  • Memory module was replaced or modified without updating the controller's loaded program.
  • Program download to controller did not update the memory module, or vice-versa.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Transfer the user program from the memory module to the controller using the programming software.

  2. 2

    Change the controller to Run mode after the program transfer is complete.

  3. 3

    Verify bit S:2/9 is correctly handled in the system logic if it's intentionally set.