0023
STI ERROR
Allen-Bradley · MicroLogix 1400 Programmable Controllers
Hva betyr 0023 ?
An error occurred in the Selectable Timed Interrupt (STI) configuration. This is a recoverable fault, meaning the controller can potentially continue operation if the error is addressed, but the STI function may not work as intended.
Vanlige årsaker
- Invalid parameters or settings within the STI configuration (e.g., interrupt time out of range).
- Conflicting STI routines or timers that interfere with each other.
- Hardware issue related to the internal timer or interrupt mechanism.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Refer to the Error Code in the STI Function File for the specific error details.
- 2
Review the STI configuration parameters and ensure they are valid, within limits, and do not conflict.
- 3
Reload the corrected STI configuration and enter Run mode.