0035

ILLEGAL INSTRUCTION IN INTERRUPT FILE

Allen-Bradley · MicroLogix 1400 Programmable Controllers

Hva betyr 0035 ?

The program contains a Temporary End (TND), Refresh (REF), or Service Communication instruction within an interrupt subroutine (STI, EII, HSC) or a user fault routine. These specific instructions are not permitted in interrupt contexts due to their system-level implications or timing characteristics. This is a nonrecoverable fault.

Vanlige årsaker

  • Unsupported instructions (TND, REF, Service Communication) are placed inside an interrupt service routine (STI, EII, HSC) or user fault routine.
  • Incorrect programming practices for interrupt service routines, violating execution rules for these contexts.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Correct the program by removing Temporary End (TND), Refresh (REF), or Service Communication instructions from all interrupt subroutines (STI, EII, HSC) and user fault routines.

  2. 2

    Recompile and reload the modified program into the controller.

  3. 3

    Enter the Run mode after the program is successfully reloaded.