ERR_SOCKET_CONNECT
Socket error during Connect operation
Allen-Bradley · MicroLogix 1400 Programmable Controllers
Hva betyr ERR_SOCKET_CONNECT ?
An error occurred during the socket connect operation. This prevents the Modbus TCP client from establishing a connection to a remote Modbus TCP server, often due to network connectivity problems or incorrect destination settings.
Vanlige årsaker
- Remote Modbus TCP server is unreachable or not listening on the specified port.
- Network connectivity issues (e.g., cable disconnected, faulty switch, firewall blocking).
- Incorrect remote IP address or port configured in the Modbus TCP client settings.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify the remote Modbus TCP server's IP address and port are correctly configured in the client settings.
- 2
Ping the remote Modbus TCP server's IP address from the controller to check network connectivity.
- 3
Ensure no firewall is blocking the Modbus TCP port (default 502) between the client and server.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: Allen-Bradley MicroLogix 1400 Programmable Controllers