7951 A810

CC limit switch %.1s-

Heidenhain · NC Control

Hva betyr 7951 A810 ?

The permissible negative traverse range for the specified axis was exceeded. This indicates the axis has moved beyond its programmed negative software limit or a physical negative limit switch has been activated.

Vanlige årsaker

  • Permissible negative traverse range exceeded.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the physical negative limit switch for the affected axis for any damage, obstruction, or incorrect adjustment.

  2. 2

    Verify the setting of parameter MP670 (Negative software limit switch) for the specified axis to ensure it is configured correctly according to the machine's travel limits.

  3. 3

    Inspect the axis position feedback system (encoder) for accuracy and potential errors that could lead to an overshoot.

  4. 4

    Manually jog the axis cautiously in the positive direction to move it off the limit switch, then verify it moves freely without mechanical binding before reaching the negative limit again.